SciELO - Scientific Electronic Library Online

 
vol.13 issue3Moisture content prediction in poultry litter to estimate bioenergy production using an artificial neural network author indexsubject indexsearch form
Home Pagealphabetic serial listing  

Services on Demand

Journal

Article

Indicators

Related links

  • Have no similar articlesSimilars in SciELO

Share


Revista mexicana de ingeniería química

Print version ISSN 1665-2738

Abstract

BELMAN-FLORES, J. M. et al. Exergetic analysis of a refrigeration system. Rev. Mex. Ing. Quím [online]. 2014, vol.13, n.3, pp.957-968. ISSN 1665-2738.

This paper presents the exergy analysis of an experimental refrigeration system that operates with the refrigerant R134a. The research is based on analyzing the influence of six operational and controllable parameters of the experimental setup such as the compressor frequency of operation, the degree of static superheat, and the temperature of the secondary fluids (at the inlet of the evaporator and the condenser) on the exergy destruction. Thus, the results show that most exergy destruction is located in the condenser, followed by the compressor, the expansion valve and the evaporator. Furthermore, the highest exergetic efficiency is obtained by a decrease in the temperature of the secondary fluid inside the evaporator, and by an operation of the compressor at low speed. The efficiency of the compressor is also included in the analysis, which is a parameter that determines the exergy destruction of the largest component. Finally, a function of the exergetic efficiency is established in order to find those magnitudes of operational parameters that contribute to improving this efficiency.

Keywords : irreversibilities; vapor compression; exergy; R134a; controllable parameters; combined efficiency.

        · abstract in Spanish     · text in English     · English ( pdf )

 

Creative Commons License All the contents of this journal, except where otherwise noted, is licensed under a Creative Commons Attribution License